SITOP PSU100C
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
27
Technical data
6
Note
For an AC input voltage, the technical data is applicable for rated input voltage, rated load
and +25° C ambient temperature (if nothing else is specified).
6.1
Input
6EP1321-5BA00
(12 V/2 A)
6EP1322-5BA10
(12 V/6.5 A)
6EP1331-5BA00
(24 V/0.6 A)
6EP1331-5BA10
(24 V/1.3 A)
Input
1-phase AC or DC
Rated voltage
U
e rated / for
AC
100...230 V
Voltage range / for AC
85...264 V
Rated voltage Ue rated / for
DC
120...230 V
Voltage range / for DC
110…300 V
Wide-range input
Yes
Overvoltage strength
2.3 x Ue rated, 1.3 ms
Power failure buffering
at Ia rated, min.
20 ms
Power failure buffering
at Ue = 230 V
Rated line frequency
50/60 Hz
Line frequency range
47...63 Hz
Input current / at rated value
of input voltage 100 V/rated
value
0.63 A
1.6 A
0.28 A
0.63 A
Input current / at rated value
of input voltage 230 V
0.31 A
0.8 A
0.18 A
0.31 A
Inrush current limiting
(+ 25 °C), max.
33 A
31 A
28 A
34 A
I²t, max.
1.2 A²·s
3 A²·s
0.7 A²·s
1.2 A²·s
Integrated input fuse
Internal
Protection in the line feeder
cable (IEC 898)
Recommended miniature circuit-breaker: Characteristic B from 16 A or characteristic C
from 10 A