Mounting position, mounting clearances
4
4.1
Standard mounting position
The device is mounted on standard mounting rails according to EN 60715 35x7,5/15. The
device must be mounted vertically in such a way that the input terminals are at the bottom
and the output terminals are at the top to ensure correct cooling.
A clearance of at least 50 mm must always be maintained above and below the device. In
the vicinity of cable ducts it is only permissible to reduce the clearance to a minimum of
25 mm (see Figure 4-1 Mounting (Page 19)).
Lateral clearances do not have to be maintained.