Technical data
6.4 Closed-loop control
SITOP modular 1ph/2ph
48
Operating Instructions, 06.2014, C98130-A7548-A1-3-7629
6.4
Closed-loop control
6EP1333-3BA10
(24 V/5 A)
6EP1334-3BA10
(24 V/10 A)
6EP1336-3BA00
(24 V/20 A)
6EP1337-3BA00
(24 V/40 A)
Dyn. line regulation
(Ue rated ±15%), max.
0,1 %
0,1 %
1 %
1 %
Dyn. load regulation
(Ia: 50/100/50%), Ua ±
typ.
3 %
3 %
2 %
2 %
Load step regulation time
50 to 100%, typ.
2 ms
2 ms
2 ms
2 ms
Load step regulation time
100 to 50%, typ.
2 ms
2 ms
2 ms
2 ms
Regulation time /
maximum
5 ms
5 ms
5 ms
5 ms
6.5
Protection and monitoring
6EP1333-3BA10
(24 V/5 A)
6EP1334-3BA10
(24 V/10 A)
6EP1336-3BA00
(24 V/20 A)
6EP1337-3BA00
(24 V/40 A)
Output overvoltage
protection
< 35 V
< 35 V
< 35 V
< 35 V
Current limitation, typ.
5.5 A
12 A
23 A
46 A
Property of the
output/short-circuit proof
Yes
Short-circuit protection
Optional constant current characteristic curve or latching shutdown
Continuous short-circuit
current / rms value /
typical
5.5 A
12 A
23 A
46 A
Overload / short-circuit
display
Yellow LED for "overload", red LED for "latching shutdown"
6.6
MTBF
6EP1333-3BA10 (24 V/5 A)
6EP1334-3BA10 (24 V/10 A)
6EP1336-3BA00 (24 V/20 A)
6EP1337-3BA00 (24 V/40 A)
Mean Time Between
Failures
SN29500:
>500000 h (typ. 700000 h) at 40° C,
rated load, 24 h operation