Installation
5.1 Line-side connection
SITOP modular 1ph/2ph
Operating Instructions, 06.2014, C98130-A7548-A1-3-7629
35
Protection
SITOP modular
Line-side protection recommended for 1-phase operation or required for 2-phase operation
6EP1333-3BA10
(24 V/5 A)
•
1-phase operation: Miniature circuit breaker (IEC 898), characteristic C (B), 6 A (10 A)
•
2-phase operation: 2-pole coupled miniature circuit breaker (IEC 898), characteristic C (B),
6 A (10 A)
or for 230 V
3RV2011-1EA10 circuit breaker, setting of the thermal current limiter: 3.8 A or
3RV2711-1ED10 circuit breaker (branch circuit protection according to UL 489)
or for 400/500 V
3RV2011-1DA10 circuit breaker, setting of the thermal current limiter: 3 A or
3RV2711-1DD10 circuit breaker (branch circuit protection according to UL 489)
6EP1334-3BA10
(24 V/10 A)
•
1-phase operation: Miniature circuit breaker (IEC 898), characteristic C (B), 6 A (10 A)
•
2-phase operation: 2-pole coupled miniature circuit breaker (IEC 898), characteristic C (B),
6 A (10 A)
or for 230 V
3RV2011-1EA10 circuit breaker, setting of the thermal current limiter: 3.8 A or
3RV2711-1ED10 circuit breaker (branch circuit protection according to UL 489)
or for 400/500 V
3RV2011-1DA10 circuit breaker, setting of the thermal current limiter: 3 A or
3RV2711-1DD10 circuit breaker (branch circuit protection according to UL 489)
6EP1336-3BA00
(24 V/20 A)
•
1-phase operation: Miniature circuit breaker (IEC 898), characteristic C, 10 A
•
2-phase operation: 2-pole coupled miniature circuit breaker (IEC 898), characteristic C, 10 A
or for 120 V
3RV2411-1JA10 circuit breaker
or for 230 V
3RV2411-1FA10 circuit breaker
6EP1337-3BA00
(24 V/40 A)
•
1-phase operation: Miniature circuit breaker (IEC 898), characteristic C, 20 A
•
2-phase operation: 2-pole coupled miniature circuit breaker (IEC 898), characteristic C, 20 A
or for 120 V
3RV2421-4BA10 circuit breaker
or for 230 V
3RV2411-1JA10 circuit breaker
The protective conductor of the line supply must be connected at the PE terminal.
Other country-specific regulations may have to be observed when installing the device.