Functions
44
7UM62 Manual
C53000-G1176-C149-3
period (2 cycles), the detected direction is stored, as long as no sufficient measuring
voltage is available. If a short circuit already exists at generator startup (or, in case of
motors or transformers, during connection), so that no voltage is present in the
memory and no direction can be determined, a trip is issued.
The direction detection can be blocked via a binary input.
Figure 2-13 indicates the I>> stage logic diagram with the direction element.
Figure 2-13
Logic Diagram of I>> Stage with Direction Element
2.7.2
Setting Hints
General
The high-current stage I>> of the overcurrent protection is only effective and
accessible if it has been assigned within the framework of configuration at
address
to either side 1 or side e, i.e. if either =
Non-dir.
Side 1 side 2
,
Dir. Side 1
or
Dir. side 2
was set.
Disabled
is selected
if the function is not needed.
If you use the direction element, make sure that the CT and VT set are consistent.
Pickup I
L1
>>
FNo. 01721
&
&
&
&
FNo. 01808
Tripping
matrix
FNo. 01809
FNo. 01803
FNo. 01802
FNo. 01801
FNo. 01956
&
&
OR
FNo. 01806
FNo. 01807
Direction
detection
non direct.
”1”
forward
reverse
undeterminable
Pickup I
L3
>>
Pickup I
L2
>>
&
&
&
FNo. 01720
U
L
I
x
OR
TMin
TRIP CMD