Functions
2.20 Auxiliary Functions
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A5, Release date 11.2012
277
2.20.4
Average Measurements
The long-term averages are calculated and output by the 7SK80.
2.20.4.1 Description
Long-Term Averages
The long-term averages of the three phase currents
I
x
, the positive sequence components
I
1
for the three phase
currents, and the real power P, reactive power Q, and apparent power S are calculated within a set period of
time and indicated in primary values.
For the long-term averages mentioned above, the length of the time window for averaging and the frequency
with which it is updated can be set.
2.20.4.2 Setting Notes
Average Calculation
The selection of the time period for measured value averaging is set with parameter
8301
DMD Interval
in
the corresponding setting group from A to D under
MEASUREMENT
. The first number specifies the averaging
time window in minutes while the second number gives the frequency of updates within the time window.
15
Min., 3 Subs
, for example, means: Time average is generated for all measured values with a window of 15
minutes. The output is updated every 15/3 = 5 minutes.
With address
8302
DMD Sync.Time
, the starting time for the averaging window set under address
8301
is
determined. This setting specifies if the window should start on the hour (
On The Hour
) or 15 minutes later
(
15 After Hour
) or 30 minutes / 45 minutes after the hour (
30 After Hour
,
45 After Hour
).
If the settings for averaging are changed, then the measured values stored in the buffer are deleted, and new
results for the average calculation are only available after the set time period has passed.
16031
ϕ
(3Vo,INs) =
MV
Angle between 3Vo and INsens.
30701
Pa =
MV
Pa (active power, phase A)
30702
Pb =
MV
Pb (active power, phase B)
30703
Pc =
MV
Pc (active power, phase C)
30704
Qa =
MV
Qa (reactive power, phase A)
30705
Qb =
MV
Qb (reactive power, phase B)
30706
Qc =
MV
Qc (reactive power, phase C)
30707
PFa =
MV
Power Factor, phase A
30708
PFb =
MV
Power Factor, phase B
30709
PFc =
MV
Power Factor, phase C
30800
VX =
MV
Voltage VX
30801
Vph-n =
MV
Voltage phase-neutral
No.
Information
Type of In-
formation
Comments
Summary of Contents for SIPROTEC 7SK80
Page 8: ...Preface SIPROTEC 7SK80 Manual E50417 G1140 C344 A5 Release date 11 2012 8 ...
Page 496: ...Literature SIPROTEC 7SK80 Manual E50417 G1140 C344 A5 Release date 11 2012 496 ...
Page 508: ...Glossary SIPROTEC 7SK80 Manual E50417 G1140 C344 A5 Release date 11 2012 508 ...
Page 512: ...Index SIPROTEC 7SK80 Manual E50417 G1140 C344 A5 Release date 11 2012 512 ...