11 M.CLe
Measurement repetition
NO
[ ] no
YES
[ ] yes
11 CHA e
Characteristic of the O/C stage IEp
inverse
[ ] Normal inverse
short in
[ ] Very inverse
extr.inv
[ ] Extremely inverse
long inv
[ ] long inverse
never
[ ] Never
11 TEp
Trip time delay inverse time O/C stage IEp
min. 0.05
s
max. 3.20
©©©©
11 CHA e
Characteristic of the O/C stage IEp
inverse
[ ] Inverse
short in
[ ] Short inverse
long inv
[ ] Long inverse
mode inv
[ ] Moderately inverse
very inv
[ ] Very inverse
extr inv
[ ] Extremely inverse
def inv
[ ] Definite inverse
IsqaredT
[ ] I-squared-t
never
[ ] Never
11 DE
Delayfactor of inverse earth-current protec.
min. 0.5
s
max. 15.0
©©©©
11 IEp
Pick-up value inverse time O/C stage IEp
min. 0.05
I/In
max. 4.00
©©©©
11IEpdy
Pick-up value inverse time E/F stage IEp (dyn)
min. 0.05
I/In
max. 4.00
©©©©
11CALC e
RMS format for inverse time O/C protection
noHARMON
[ ] Without harmonics
HARMONIC
[ ] With harmonics
11 M.CLe
Manual close
IE>>unde
[ ] IE>> undelayed
IE>undel
[ ] Ie> undelayed
IEp unde
[ ] IEp undelayed
INEFFECT
[ ] Ineffective
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
24 UNBAL LOAD - UNBALANCED LOAD PROTECTION
24 UNB.L
State of the unbalanced load protection
ON
[ ] on
OFF
[ ] off
24 I2>
Pick-up value of neg. seq. I low-set stageI2>
min. 8
%
max. 80
©©©©
24 TI2>
Trip delay of neg. seq. I low-set stage TI2>
min. 0.00
s
max. 60.00
©©©©