$SSHQGL[
6-
9
&*&
10 CHAph
Characteristic of the O/C stage Ip
inverse
[ ] Inverse
short in
[ ] Short inverse
long inv
[ ] Long inverse
mode inv
[ ] Moderately inverse
very inv
[ ] Very inverse
extr inv
[ ] Extremely inverse
def inv
[ ] Definite inverse
IsqaredT
[ ] I-squared-t
never
[ ] Never
10 D
Delayfactor of inverse phase-current protec.
min. 0.5
s
max. 15.0
©©©©
10 Ip
Pick-up value inverse time O/C stage Ip
min. 0.1
I/In
max. 4.0
©©©©
10 Ip dy
Pick-up value inverse time O/C stage Ip (dyn)
min. 0.1
I/In
max. 4.0
©©©©
10CALCph
RMS format for inverse time O/C protection
noHARMON
[ ] Without harmonics
HARMONIC
[ ] With harmonics
10M.CLph
Manual close
I>>undel
[ ] I>> undelayed
I>undela
[ ] I> undelayed
Ip undel
[ ] Ip undelayed
INEFFECT
[ ] Ineffective
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
11 O/C EARTH - O/C PROTECTION EARTH FAULTS
11 O/C e
O/C protection for earth faults
ON
[ ] on
OFF
[ ] off
11 IE>>
Pick-up value of the high-set stage IE>>
min. 0.05
I/In
max. 25.00/Ñ ©©©©
11IE>>dy
Pick-up value of high-set E/F stage IE>> (dyn)
min. 0.05
I/In
max. 25.00/Ñ ©©©©
11 TIE>>
Trip time delay of the high-set stage IE>>
min. 0.00
s
max. 60.00
©©©©
11 IE>
Pick-up value of the overcurrent stage IE>
min. 0.05
I/In
max. 25.00/Ñ ©©©©
11 IE>dy
Pick-up value of def. time E/F stage IE> (dyn)
min. 0.05
I/In
max. 25.00/Ñ ©©©©
11 TIE>
Trip time delay of the overcurrent stage IE>
min. 0.00
s
max. 60.00
©©©©
www