Manual 7SJ46
Technical Data
C53000-K1174-C002-4
63
2.11
Technical Data
General device data
Current inputs
Power supply
Output relays
UL-Listing for relay output with the following rated data:
120 Vac
Pilot duty, B300
240 Vac
Pilot duty, B300
240 Vac
5 A General Purpose
24 Vdc
5 A General Purpose
48 Vdc
0.8 A General Purpose
240 Vdc
0.1 A General Purpose
120 Vac
1/6 hp (4.4 FLA)
240 Vac
1/2 hp (4.9 FLA)
Rated frequency f
N
50 Hz or 60 Hz (adjustable)
Rated current, normal earth
current I
N
1 A or 5 A
Power consumption
– at I
N
= 1 A
approx. 0.01 VA at I
N
– at I
N
= 5 A
approx. 0.2 VA at I
N
Rating of current transformer circuit
– thermal (rms)
100·I
N
for 1 s
30·I
N
for 10 s
4·I
N
continuous
– dynamic (peak value)
250·I
N
for one half-cycle
Input voltage range
24 V DC to 250 V DC (+/- 20%)
60 V AC to 230 V AC (–20%, +15%)
Power consumption
approx. 1,5 W DC
approx. 3 VA AC at U
H
= 110 V
approx. 5.5 VA AC at U
H
= 230 V
Number
2 (NO contacts), 1 live status contact
Switching capability
MAKE 1000 W/VA
BREAK 30 VA
40 W resistive load
25 VA at L/R
≤
50 ms
Switching voltage
≤
250 V DC,
≤
240 V AC
Permissible current per contact
5 A continuous;
30 A for 0.5 s (inrush current)