3 Mounting and Commissioning
456
7SD5 Manual
C53000-G1176-C169-1
Table 3-3
Jumper settings of the
Life Contact
on the input/output board C-I/O-1
Depending on the device version the contacts of some binary outputs can be changed
from normally open to normally closed (see Appendix, under Section A.2).
• In versions 7SD5***-*
D/H/M
(housing size
1
/
1
with 32 binary outputs) this is valid for
the binary outputs BO16 and BO24 (Figure 3-4, slot 19 left and right);
• In versions 7SD5***-*
C
/
G
/
L
(housing size
1
/
1
with 24 binary outputs) this is valid for
the binary output BO16 (Figure 3-4, slot 19 right);
• In versions 7SD5***-*
P
/
R
/
T
(housing size
1
/
1
with 32 binary outputs and command
acceleration) this is valid for the binary output BO24 (Figure 3-4, slot 19 left).
Table 3-4 shows the jumper settings for the contact mode.
Table 3-4
Jumper settings for contact mode of the binary outputs BO16 and BO24 on the input/output board C–I/O-1
Interchangeable
Cannot be
changed
Fuse
T2H250V
T4H250V
Jumper
Open in Quiescent State
(NO)
Closed in Quiescent State
(NC)
Factory Setting
X40
1-2
2-3
2-3
Jumper
Nominal Voltage
60/110/125 VDC
110/125/220/250 VDC 115 VAC
24/48 VDC
Device
7SD5***–*
Printed Circuit
Board
For
Jumper Open in Quies-
cent State (NO)
Closed in Quiescent State
(NC)
Factory
Setting
D/H/M
Slot 19 left side BO 16
X40
1-2
2-3
1-2
Slot 19 right
side
BO 24
X40
1-2
2-3
1-2
C/G/L
Slot 19 right
side
BO 16
X40
1-2
2-3
1-2
P/R/T
Slot 19 left side BO 24
X40
1-2
2-3
1-2
www
. ElectricalPartManuals