Motor Protection Example
illustrates an example of a complete motor protection characteristic. Such characteristic usually
consists of different protection elements, and each element is responsible for special motor malfunctions.
These are:
•
Thermal overload protection: to avoid overheating of the motor due to inadmissible load
•
Load jam protection: to prevent overheating and mechanical damage due to a locked rotor
•
Motor starting protection: protects the motor against prolonged startup procedures and the consequent
thermal overload of the rotor
•
Overcurrent and high-current elements: for motor shutdown due to electrical faults
[motorbelastungsgrenze, 1, en_US]
Figure 2-64
Example of a complete motor protection characteristic
Example:
Motor with the following data:
Nominal voltage
U
Nom
= 10 kV
Nominal current
Ι
Nom
= 436 A
Long-term current rating
Ι
max
= 135 A
Startup duration
T
startmax
= 8.5 s
Current transformer
Ι
NomCTprim
/
Ι
NomCTsec
= 500 A / 1 A
The setting for address 4402
Load Jam I>
as secondary value is calculated as follows:
Functions
2.8 Motor Protection
160
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...