Configuration
8.3 Device/hardware configuration in the TIA Portal
SIPLUS HCS4200
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
69
8.3.3.2
Configuration parameters for I/O modules
The configuration parameters are directly assigned to the respective I/O modules and are set
during device configuration. They are transferred on start-up and during re-parameterization.
PM4000 Temperature parameters
Description
Range of values
Analog channel 1 measuring range
…
Analog channel 4 measuring range
•
Not connected (default)
•
0...20 mA
•
4...20 mA (open-circuit detection)
Temperature channel 1 sensor type
Temperature channel 3 sensor type
•
None (default)
•
Pt 100
•
Pt 100 (four-wire)
•
Pt 1000
•
Pt 1000 (four-wire)
•
Type J thermocouple
•
Type K thermocouple
•
Type L thermocouple
Temperature channel 2 sensor type
Temperature channel 4 sensor type
•
None (default)
•
Pt 100
1)
•
Pt 1000
1)
•
Type J thermocouple
•
Type K thermocouple
•
Type L thermocouple
Compensation procedure
•
No compensation (default)
•
Internal sensor
•
External value
1)
When setting Pt 100/1000 (four-wire) for temperature channel 1 / 3, "none" must be selected for
temperature channel 2 / 4.