Wiring of connectors Q0-X1.1, Q0-X1.2, Q0-X1.3
Removing the transport block from the undervoltage release
Undervoltage release (-Y7)
available?
The vacuum circuit-breaker with an undervoltage release (-Y7) 3AX1103 is supplied
with a transport securing device.
• Remove the cover (see “Removing and mounting covers” page 35).
• Shift the locking screw of the striker pin from position A to B (see instructions in
operating mechanism of the vacuum circuit-breaker or on the label of the under-
voltage release).
• Mount the cover again in the reverse order (refer to “Removing and mounting
• Remove the cover for the low-voltage interface (refer
to “Removing and mounting covers” page 35).
• Insert flat-head screwdriver (size 0.5 mm x 3 mm)
into the plug (WAGO 231-110/026-000).
• Insulation-stripped connecting lead (or with wire end
ferrule) with a cross-section
- Single-core from 1.5 mm
2
to 2.5 mm
2
- Insert finely stranded core from 1.5 mm
2
to
2.5 mm
2
• Remove flat-head screwdriver.
Fig. 51
Example - wiring the 30-pole connector strip
(33)
Fig. 52
Removing the transport block
B
A
Summary of Contents for SION 3AE6113-0