  2.  Pull the lower parts of the X01 and X02 connectors 

downward. 

 

Fig. 3

 

Pulling the lower parts of the connectors
downward 

   

 

 Note 

 

Nuts and washers may fall into the drive of the SION

® 

vacuum circuit breaker. 

Secure nuts and washers so that they do not fall down. 

   

3.  If necessary, secure nuts (x4) and washers (x8) 

using a magnetic socket, to ensure that they do not 
fall down and disassemble them. 

4. 

Pull the upper parts of the X01 and X02 connectors 
upward. 

Fig. 4

 

Disassembling the upper parts of the con-
nectors 

   

Assembly 

Assembly is carried out in reverse order and should be performed using new self-locking nuts (from the accesso-
ries pack). 

Tighten the Phillips screws using a tightening torque of 1.4 ±0.1 Nm. Exceeding the tightening torque will result in 
damage to the plug flanges. 

 