2. Pull the lower parts of the X01 and X02 connectors
downward.
Fig. 3
Pulling the lower parts of the connectors
downward
Note
Nuts and washers may fall into the drive of the SION
®
vacuum circuit breaker.
Secure nuts and washers so that they do not fall down.
3. If necessary, secure nuts (x4) and washers (x8)
using a magnetic socket, to ensure that they do not
fall down and disassemble them.
4.
Pull the upper parts of the X01 and X02 connectors
upward.
Fig. 4
Disassembling the upper parts of the con-
nectors
Assembly
Assembly is carried out in reverse order and should be performed using new self-locking nuts (from the accesso-
ries pack).
Tighten the Phillips screws using a tightening torque of 1.4 ±0.1 Nm. Exceeding the tightening torque will result in
damage to the plug flanges.