Cable definition
Definition:
● Signal cables (example)
– Data cables (Ethernet, PROFIBUS, sensor cables, etc.)
– Digital I/Os
– Cables for safety functions (emergency stop, enabling)
● Power cables (example)
– Low-voltage supply lines (230 VAC, +24 VDC, etc.)
– Motor cables
Rules for routing cables
In order to achieve the greatest possible EMC compatibility for the complete system (control,
power unit, machine), the following EMC measures must be carefully observed:
● If necessary, signal and power cables may cross one another (if possible at an angle of
90°), but must never be laid close or parallel to one another.
● Only use cables approved by SIEMENS for the signal lines from and to the Control Unit.
● Signal cables must not be routed close to strong external magnetic fields (e.g. motors and
transformers).
● If signal lines cannot be routed a sufficient distance away from other cables, they must be
installed in grounded cable ducts (metal).
● The operator panel fronts, MCPs, MPPs, and full keyboards must be installed in metallically
enclosed EMC-compatible housings.
Note
For further information on interference suppression measures and the connection of
shielded cables, please refer to the EMC Installation Guide.
7.2.4
SINUMERIK_SouthKorea_Note
EMC limit values in South Korea
The EMC limit values to be complied with for South Korea correspond to the limit values of the
EMC product standard for variable-speed electric drives EN 61800-3, Category C2, or limit
value class A, Group 1 according to EN 55011. By applying suitable supplementary measures,
the limit values according to Category C2 or according to limit value class A, Group 1, are
Technical data
7.2 Supplementary electrical conditions
TCU 30.3
78
Manual, 09/2017, A5E40874197
Summary of Contents for SINUMERIK 840D sl TCU 30.3
Page 18: ...Description 2 4 Rating plate TCU 30 3 18 Manual 09 2017 A5E40874197 ...
Page 32: ...Connection 4 1 Pin assignment of the interfaces TCU 30 3 32 Manual 09 2017 A5E40874197 ...
Page 72: ...Networking 5 4 Service and diagnostics TCU 30 3 72 Manual 09 2017 A5E40874197 ...