![Siemens Sinteso FD20 Product Data Download Page 99](http://html.mh-extra.com/html/siemens/sinteso-fd20/sinteso-fd20_product-data_383408099.webp)
Special detectors
Linear smoke detector FDL241-9
10
008164_y_en_--
99 | 152
Type
Designation
Order number
Weight [kg]
DLR1193
Reflector for short distance (foil)
BPZ:4787840001
0.025
FDLU291
Adjustment kit for linear smoke
detector
A5Q00004905
0.840
RE10
Detector tester for linear smoke
detectors
BPZ:3685190001
0.345
TF04
Alarm test filter (absorption 77 %)
BPZ:4931090001
0.005
10.1.3 Technical data
Linear smoke detector FDL241-9
Operating voltage addressed / collective
DC 12…33 V / DC 14…28 V
Operating current (quiet) addressed / collective
0.8 mA / 0.7 mA
Number of external alarm indicators that can
be connected
2
Detection distance
10…100 m
Operating temperature
-25…+60 °C
Storage temperature
-30…+75°C
Air humidity (no moisture condensation)
≤
95 % rel.
Communication protocol
FDnet or collective (with and without current limitation)
Conductor cross section
0.2…1.5 mm²
Color
~RAL 9010 pure white
Protection category (IEC 60529)
IP65
Standards
EN 54-12
1
, EN 54-17, EN 62471
(
1
with detection distance of 10…100 m)
Approvals
●
VdS
●
LPCB
●
FM
G204063
126bd/02
3029351
System compatibility
●
FDnet
●
C-NET
FS20, AlgoRex, SIGMASYS
FS720, FC360
Collective system compatibility
CZ10, BC10, FC10, XC10, CS11, FC700A, FC330A,
SIGMASYS, BMS, SM80/88/D100
Detector heating unit DLH1191A
Operating voltage
DC 20…33 V
Operating current (quiescent)
30…50 mA
Resistance
600
Ω