![Siemens Sinteso FD20 Product Data Download Page 67](http://html.mh-extra.com/html/siemens/sinteso-fd20/sinteso-fd20_product-data_383408067.webp)
Alarm devices in the FDnet
Sounder base FDSB29x
7
008164_y_en_--
67 | 152
7.1.3 Technical data
Supply
FDS221-R, FDS221-W
FDSB291
FDSB292
Operating voltage
DC 12...33 V
DC 12...33 V
Operating current (quiescent)
●
Sound activated
Max. 250 µA
3.5 mA
Max. 150 µA
1.2 mA
Sounds
11
2 alarm levels
3 sound levels
11
2 alarm levels
2 sound levels
1
1 alarm level
1 sound level
Sound level
80…99 dB(A)
80…88 dB(A)
84 dB(A)
Ext. Alarm indicator (AI)
2
1
Operating temperature
-25…+70°C
-25…+70°C
(observe point detector data)
Storage temperature
-30…+75°C
-30…+75°C
Air humidity
≤
95 % rel.
≤
95 % rel.
Communication protocol
FDnet
FDnet
Collective
Conductor cross-section on
detector base
According to detector base
0.2…1.5 mm
2
Color
~RAL 3000 flame red
~RAL 9010, pure white
~RAL 9010, pure white
Protection category (IEC 60529)
with
●
Base FDB221 or FDB222
●
Base attachment FDB291
●
Base FDB221 and sealing
element FDBZ295
●
Base attachment humid
FDB293, base attachment wet
FDB295
Wall mounting with feed line
from below
→
IP43, otherwise IP40
IP44
IP54
IP43
-
-
-
-
Standards
EN 54-3, EN 54-17
EN 54-3
Approvals
●
VdS
●
LPCB
●
FM
●
DNV GL (marine)
G204073
531p
3029351
MEDB00003UV
G204062
531u
3029351
MEDB00003UV
System compatibility FDnet
FS20, AlgoRex, SIGMASYS
FS20, AlgoRex,
SIGMASYS
-