Siemens Sinteso Cerberus PRO FDA221 Manual Download Page 2

2
Building Technologies

A6V10331032_j_en_--

Fire Safety

2019-01-24

 Properties

  Extended optical detection thanks to dual wavelengths (blue and infrared): The

aspirating smoke detectors FDA241 and FDA221 use dual-wavelength technology to

trigger an alarm at the earliest possible moment. They are designed to protect small and

medium-sized business-critical environments for monitoring areas of up to 800 m

2

(FDA241) or 500 m

2

 (FDA221). The detectors continually suck in air through a pipe

system via their aspirating holes. The air is fed into a uniquely designed detection

chamber, in which tiny smoke particles are detected by scattered light.

  Lower mounting and service costs: The aspirating smoke detectors FDA241 and

FDA221 can be used on an FDnet/C-NET detector line. For this purpose, communication

transponder FDCC221S is required.

  Configuration using the USB interface or the control panel via FDCC221S (optional): All

detector configurations, maintenance work, and alarm and fault management processes

can be carried out at a central location – the fire control panel. This ensures better

control while also reducing the costs of the overall solution.

  'Out-of-the-box' mounting and commissioning: Installation is simple thanks to combined

functions for normalizing smoke values and airflow, as well as appropriate presettings for

alarm and fault thresholds.

  ASD filter box FDAZ292 available as an accessory: Dust and other dirt is filtered out of

the aspirated air and does not get into the aspirating smoke detector. The filters in the

ASD filter box are easy to replace.

Use

Aspirating smoke detectors are used for early detection of smoke-generating fires in rooms

and equipment. They are especially suited to applications in which point detectors are

pushed to their limits, cannot be used or can only be used with restrictions.
The aspirating smoke detector continually takes air from the monitored room using a

connected pipe system with defined aspirating holes. The air is supplied to the detection

chamber and is analyzed for smoke particles using the detector installed there. The

sensitivity of the detector can be adjusted.
The position and size of the aspirating holes are calculated with the 'FXS2056 ASD Asyst

Tool V2' software. The calculation ensures that the air passes from the aspirating hole to the

detector in the time specified and with the required calculated sensitivity.

The 'FXS2056 ASD Asyst Tool V2' software is replacing the 'FXS2055 ASD Asyst Tool'

software.

Examples of application

  Cavities such as false ceilings or false floors

  Clean rooms

  Rooms the height of which is greater than that permitted for point detectors

  Rooms with electromagnetic fields which influence the function of point detectors

  Large rooms up to 800 m²

  Separate monitoring of control cabinets and electronics cabinets

  Data centers

  Telecommunication centers

  Mounting lines

  Cable tunnels

  Conveyor belts

Summary of Contents for Sinteso Cerberus PRO FDA221

Page 1: ...on Patented technology Early detection of a wider spectrum of particle sizes in the air Configuration using the USB interface or the control panel via FDCC221S optional ASD Asyst Tool software to assist with pipe configuration Unique dust resistant detection chamber Intuitive front indicator for airflow and smoke value Access to service functions Different event protocols Offline online configurat...

Page 2: ...lds ASD filter box FDAZ292 available as an accessory Dust and other dirt is filtered out of the aspirated air and does not get into the aspirating smoke detector The filters in the ASD filter box are easy to replace Use Aspirating smoke detectors are used for early detection of smoke generating fires in rooms and equipment They are especially suited to applications in which point detectors are pus...

Page 3: ...industry Subway stations Agricultural operations All other applications with visible dust load Functions Indication The display contains clear comprehensible bar graphs for smoke and airflow as well as an alarm indicator an error indicator and a dust indicator FDA241 When the housing cover is open the operator has access to the Reset Normalize Smoke and Normalize Flow functions as well as the mini...

Page 4: ...amage to the connection cable when positioning the housing cover make sure that the connection cable has been routed correctly The service area for the detector can be accessed in two ways Partial access Remove the two screws on the top of the detector Slide the housing cover up until you hear it snap into place Full access Remove the two screws on the top of the detector Slide the housing cover u...

Page 5: ...ip or a watchmaker s screwdriver to press the button in the opening Once you have finished with this function press the button in the opening again The smoke detector uses standard values for monitoring during normalization Normalization of the smoke density To determine the nominal air quality in relation to the smoke density perform this function during commissioning The nominal value establishe...

Page 6: ... NET the alarms and the associated relays are not reset USB connection You can use a mini USB cable to connect the detector to a Windows PC To set up the detector use the configuration tool FXS2051 ASD Configuration Tool Test function LED Hold the Buzzer silence button down for 5 seconds The LEDs on the display are tested with 3 different brightness settings If the aspirating smoke detector is to ...

Page 7: ... and a yellow LED With potential free relay contacts for fault messages Additional installation of an I O module possible Uninterruptible power supply with battery charging Batteries max 17 Ah Dimensions W x H x D 430 x 399 x 124 mm Battery FA2003 A1 12 V 7 Ah VdS For supplying fire control panels and aspirating smoke detectors with power Compatible with Fire control panels for the Sinteso and Cer...

Page 8: ...ll find more information in document A6V10916366 FDAZ292 ASD filter box Filter box for installation in the pipe system for aspirating smoke detectors Filters dust and other dirt out of the air aspirated by the aspirating smoke detector Minimizes internal contamination of the aspirating smoke detector Contains filter set FDAZ292 AA with three filters coarse medium fine Compatible with the aspiratin...

Page 9: ...tector FDA241 FDA221 A6V10393194 Technical manual Power supply kit A 70 W FP120 Z1 A6V10345654 Installation Mounting Aspirating Smoke Detectors FDA241 FDA221 A6V10340094 User Manual ASD Asyst Tool FXS2055 A6V10728226 User Manual ASD Asyst Tool V2 FXS2056 A6V10334435 Planning Installation ASD Pipe system A6V10332759 Installation Operation Manual Configuration ASD Configuration Tool FXS2051 A6V10877...

Page 10: ...ust correspond to the calculation made using the FXS2056 ASD Asyst Tool V2 software Air intake exhaust pipe Metric 25 mm outer diameter OD Monitoring area dependent on local provisions and standards Up to 800 m Up to 500 m System compatibility Compatible with all Siemens FC20 FC720 FS20 FS720 systems Relay alarm outputs Can be selected with without lock Nominal current 2 0 A at DC 30 V Contact NO ...

Page 11: ...latile event memory with time and date stamp for smoke density airflow detector status and faults Normalization of smoke value and airflow Setting of threshold values for smoke alarms and faults User setting for normalization of smoke density and airflow Preset values are retained during the normalization period Warranty period 2 years Approvals VdS FDA241 G213050 FDA221 G213050 1 A weighted sound...

Page 12: ...0 or http siemens com bt download 13 FDA221 FDA241 Aspirating smoke detector for use in fire detection and fire alarm systems installed in buildings 305 2011 EU CPR EN 54 20 EN 54 17 2014 30 EU EMC EN 50130 4 EN 61000 6 3 2011 65 EU RoHS EN 50581 DoP No 0786 CPR 21270 DoC No CED FDA221 FDA241 FDA221 FDA241 0786 Siemens Schweiz AG Theilerstrasse 1a CH 6300 Zug Technical data see doc A6V10334410 The...