The following menu contains the pick lists to select the variables to be displayed on the front
panel default display.
Table 6-93
Display Parameters Menu (8000) Parameters
Parameter
ID
Default
Description
Status variable 1
8001
DEMD
Select variable 1 to display on the LCD display.*
Status variable 2
8002
%SPD
Select variable 2 to display on the LCD display.*
Status variable 3
8003
VLTS
Select variable 3 to display on the LCD display.*
Status variable 4
8004
ITOT
Select variable 4 to display on the LCD display.*
Status variable 5
8005
IMRF
Select variable 5 to display on the Tool
1
display.*
Status variable 6
8006
IMRF
Select variable 6 to display on the Tool
1
display.*
Status variable 7
8007
IMRF
Select variable 7 to display on the Tool
1
display.*
* See Table Pick list variables for the front display.
1
Available for drive tool only.
Table Pick list variables for the front display contains the abbreviation, variable name, units and
description of the standard pick list variables used in menus such as the Historic Log Menu or the
Display Variable Menu.
The variable name column contains the name of the display variable. The content of the variable
name column is displayed as you scroll through the list of available display variables.
The abbreviation column contains an abbreviation that is displayed after a variable is selected
from the list. The abbreviation is between 3 and 4 characters in length and is displayed on the
front panel of the drive.
Table 6-94
Pick list variables for the front display
Abbreviation Variable Name
Units
Description
IMRF
Mag current ref
A
Output I
ds
reference.
ITRF
Trq current ref
A
Output I
qs
reference.
FLDS
Flux DS
%
Motor Flux DS. Main flux component, magnitude of flux
vector.
FLQS
Flux QS
%
Motor Flux QS. Quadrature component; normally close to
or at zero.
VDRF
Vds reference
%
Motor V
ds
reference. Direct component.
VQRF
Vqs reference
%
Motor V
qs
reference. Quadrature component.
SLIP
Slip frequency
%
Motor slip frequency.
%SPD
Motor speed
%
FREQ
Output Frequency
Hz
RPM
Motor speed
rpm
Motor speed with slip correction.
VLTS
Motor voltage
V
IMAG
Mag current filtered
A
Motor I
ds
filtered. Motor voltage producing current.
ITRQ
Trq current filtered
A
Motor I
qs
filtered. Torque producing current.
ITOT
Motor current
A
Motor total motor current.
Parameter Assignment/Addressing
6.17 Options for Meter Menu (8)
Control Manual
162
Operating Manual, A5E50491925A
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......