Operation
8.2 Standard mode settings
Installation and Operating Instructions SINAMICS G180
136
Operating Instructions, 02/2019, 4BS0751-007
Control behavior for "Remote" (static)
●
Control the operation of "Speed on" with a switch at -X2:10.
●
Enter the setpoint via control cable terminal block -X2 with analog setpoint value 1.
●
When required use the reversing input -X2:16.
"Local" and "Remote" mode
●
"Emerg. stop (NC)": If you open the contact at -X2:15, the drive decelerates down to 0
speed along the braking ramp for a fast stop. The converter clears all self-latching
functions.
●
"Reset" (NO): Reset faults and "Fast stop" using a 24 V pulse at -X2:14.
●
"Controller release, static " (NC) -X2:8: Enable the converter using a permanent contact.
The drive coasts to a stop if you open the contact. The converter clears all self-holding
functions.
8.2.2
Mode "std sisd"
(D)
Dynamic: Pushbutton mode
(S)
Static: Switch mode
Figure 8-4
Assignment of the control cable terminals for operation of "std sisd"
Operation different from "std siss"
The operation "Speed On" for "Remote" mode is dynamic.
Start the drive with an NO (normally open) contact at -X2:11. You change the converter
speed to 0 with an NC (normally closed) contact at -X2:10.