p1106[0...n]
CI: Minimum speed signal source / n_min s_s
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: p2000
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 3050
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for lowest possible motor speed.
Dependency:
See also: p1080
NOTICE
The effective minimum speed is formed from p1080 and p1106.
p1108[0...n]
BI: Total setpoint selection / Total setp sel
Access level: 4
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 3030
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to select the total setpoint.
Dependency:
The selection of the total speed setpoint is automatically interconnected to the status word of the technology controller
(r2349.4) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
If the "hibernation mode" function is activated (p2398 = 1), an interconnection is made to r2399.7.
See also: p1109
CAUTION
If the technology controller is to supply the total setpoint using p1109, then it is not permissible to disable the
interconnection to its status word (r2349.4).
If the "hibernation mode" function is activated, then it is not permissible to disable the interconnection to status word
r2399.
p1109[0...n]
CI: Total setpoint / Total setp
Access level: 4
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: p2000
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 3030
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the total setpoint.
For p1108 = 1 signal, the total setpoint is read in via p1109.
Dependency:
The signal source of the total setpoint is automatically interconnected to the output of the technology controller (r2294)
if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
If the "hibernation mode" function is activated (p2398 = 1), an interconnection is made to r2397[0].
See also: p1108
CAUTION
If the technology controller is to supply the total setpoint using p1109, then it is not permissible to disable the
interconnection to its output (r2294).
If the "hibernation mode" function is activated, then it is not permissible to withdraw the interconnection to setpoint
r2398[0].
Parameters
7.2 Parameter list
SINAMICS G120X converter
630