Commissioning
4.3 Connecting the inverter to the fieldbus
CU230P-2 Control Units
Compact Operating Instructions, 01/2016, A5E37058917B AA
45
Control word
Parameter
BACNet Meaning
r2090 .00 p0840 BV20
ON/OFF1
Switch on motor
.01 p0844 BV27
No OFF2
Precondition in order to be able to switch on
the motor (ON command).
.02 p0848 BV28
No quick stop
(OFF3)
.03 p0852 BV26
Enable operation
.04 p1140 BV26
Do not disable
RFG
The ramp-function generator can be enabled
.05 p1141 BV26
Enable RFG
The output of the ramp-function generator
follows the setpoint
.06 p1142 BV26
Enable setpoint
Motor accelerates with the ramp-up time p1120
to the setpoint
.07 p2103 BV22
Acknowledge
faults
.08
,
.09
---
N/A
Reserved
.10 p0854 BV93
Master control by
PLC
Control via fieldbus, the inverter accepts the
process data from the fieldbus
.11 p1113 BV21
Direction reversal Invert setpoint in the inverter
.12 ---
N/A
Reserved
.13 p1035 N/A
MOP raise
Increase the setpoint saved in the motorized
potentiometer
.14 p1036 N/A
MOP lower
Reduce the setpoint saved in the motorized
potentiometer
.15 ---
N/A
Reserved