Commissioning
4.3 Connecting the inverter to the fieldbus
CU230P-2 Control Units
40
Compact Operating Instructions, 01/2016, A5E37058917B AA
4.3.1
PROFINET and PROFIBUS
Examples for telegrams via PROFIBUS and PROFINET
Telegram 1:
STW1
Control word 1
ZSW1
Status word 1
PZD01/02 Process data 16-bit
NSOLL_A Speed setpoint
NIST_A
Speed actual value
Telegram 20:
STW1
Control word 1
IAIST_GLATT Smoothed current actual value
ZSW1
Status word 1
MIST_GLATT
Smoothed torque
PZD01/02
Process data 16-bit PIST_GLATT
Smoothed active power
NSOLL_A
Speed setpoint
MELD_NAMUR Control word according to the
VIK-NAMUR definition
NIST_A_GLATT Smoothed actual
speed value
Control word 1 (STW1), PZD receive word 1 (word: r2050[0], bits: r2090.00 … r2090.15)
Bit Meaning
Explanation
0
0 = OFF1
The motor brakes with the ramp-down time p1121 of the ramp-function generator.
The inverter switches off the motor at standstill.
0
→ 1 = ON
The inverter goes into the "ready" state. If, in addition bit 3 = 1, then the inverter
switches on the motor.
1
0 = OFF2
Switch off the motor immediately, the motor then coasts down to a standstill.
1 = No OFF2
Precondition in order to be able to switch on the motor using bit 0 (ON command).
2
0 = Quick stop (OFF3)
The motor brakes with the OFF3 ramp-down time p1135 down to standstill.
1 = No quick stop (OFF3)
Precondition in order to be able to switch on the motor using bit 0 (ON command).
3
0 = Inhibit operation
Switch off the motor immediately
→ motor coasts down to a standstill.
1 = Enable operation
Precondition in order to be able to switch on the motor using bit 0 (ON command).
4
0 = Disable RFG
The inverter immediately sets its ramp-function generator output to 0.
1 = Do not disable RFG
The ramp-function generator can be enabled.
5
0 = Stop RFG
The output of the ramp-function generator stops at the actual value.
1 = Enable RFG
The output of the ramp-function generator follows the setpoint.