Commissioning
4.2 Commissioning with BOP-2 operator panel
CU230P-2 Control Units
Compact Operating Instructions, 01/2016, A5E37058917B AA
37
10.
Select the default setting for the interfaces of the inverter that is suitable
for your application.
Preassignment of the interfaces (Page 16)
11.
Minimum and maximum motor speed
12.
13.
Scaling of analog input 0
14.
Motor ramp-up time
15.
Motor ramp-down time
16.
Ramp-down time for the OFF3 command
17.
Motor data identification
Select the method which the inverter uses to measure the data of the
connected motor:
OFF
Motor data is not measured.
STIL ROT Recommended setting: Measure the motor data at standstill
and with the motor rotating. The inverter switches off the
motor after the motor data identification has been complet-
ed.
STILL
Measure the motor data at standstill. The inverter switches
off the motor after the motor data identification has been
completed.
Select this setting if one of the following cases is applicable:
•
You have selected the control mode "SPD N EN".
However, the motor cannot rotate freely – for example, if
the traversing range is mechanically limited.
•
You have selected U/f control as control mode, e.g.
"VF LIN" or "VF QUAD".
ROT
Measuring the motor data while it is rotating. The inverter
switches off the motor after the motor data identification has
been completed.
18.
Complete quick commissioning:
18.1. Switchover the display using an arrow key: nO
→
YES
18.2. Press the OK key.
You have completed quick commissioning.