Spare parts and accessories
7.2 Optional accessories
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
89
7.2.5
Output reactor
Output reactors reduce the voltage stress on the motor windings and the load placed on the
converter as a result of capacitive recharging currents in the cables.
When using a output reactor, observe the following restrictions:
●
The output frequency must not exceed 150 Hz.
●
The pulse frequency must not exceed 4 kHz.
NOTICE
Damage to the output reactor by exceeding the maximum pulse frequency
The maximum permissible pulse frequency when using the output reactor is 4 kHz. The
output reactor can be damaged if the pulse frequency is exceeded.
•
When using an output reactor, the pulse frequency of the Power Module must not be
higher than 4 kHz.
NOTICE
Damage to the output reactor if it is not activated during commissioning
The output reactor may be damaged if it is not activated during commissioning.
•
Activate the output reactor during commissioning via the parameter specified by the
converter manufacturer.
•
Activate the output reactor during commissioning according to the electric specifications.
Mounting position