Installing
3.2 EMC-compliant installation of a machine or system
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
21
Figure 3-2
Grounding and high-frequency equipotential bonding measures in the control cabinet
and in the plant/system
Further information
Additional information about EMC-compliant installation is available in the Internet:
EMC installation guideline
http://support.automation.siemens.com/WW/view/en/60612658
3.2.2
Cables
Cables with a high level of interference and cables with a low level of interference are
connected to the converter:
●
Cables with a high level of interference:
–
Cable between the line filter and converter
–
Motor cable
–
Cable at the converter DC link connection
–
Cable between the converter and braking resistor
●
Cables with a low level of interference:
–
Cable between the line and line filter
–
Signal and data cables