Options
11.98
9-4
ENGLISH
Siemens AG 6SE7087-6AC85-0AA0
Common Rectifier Operating instructions
Current input of DC 24V power supply:
The figures are required in addition to the 1A consumed
by the basic unit.
(In case of size B, the demand of the basic unit
increases from 0,5A to 1A, owing to the fan required).
9.3 Power
Supply
A SITOP power supply as described in Catalog KT10 is recommended for the common rectifier (connector X9).
9.4
Actual-current sensing module
Z = K91
Order-No. for retrofit assembly: 6SE7090-0XC85-1TD0
Unit
Jumper
I
rated output
R
i total
Size
[
A
]
[
Ω
]
E
J14
605
33,222
J13
536
37,507
J12
463
43,432
J11
420
47,886
J10
375
53,647
J9 354
56,849
J8 270
74,557
J7 235
85,677
J6 222
90,720
J5 173
116,421
J4 142
141,887
B and C
J3
94
214,464
J2 86
234,523
J1 72
280,230
keine
41
492,381
Table 9.6
Jumpers for actual-current sensing module
Boards
Current drain
(mA)
24V DC supply
CB1 190
CBP 150
CB2 100
CBC 100
SCB1 50
SCB2 150
T100 550
T300 without tacho
620
Table 9.5
Current drain of the option boards
www