11.98
Technical data
Siemens AG 6SE7087-6AC85-0AA0
ENGLISH
14-1
Common Rectifier Operating instructions
14 Technical
data
In the event of conditions of use other than those listed in this chapter, please contact your local Siemens
branch or national subsidiary.
Coolant temperature
0 °C to +40 °C
Storage temperature
−
25 °C to +70 °C
Transport temperature
−
25 °C to +70 °C
Environmental class
3K3
DIN IEC 60721-3-3 / 04.90
Soiling
2
DIN VDE 0110 Part 1 / 01.89
moisture not permitted
Overvoltage category (power section)
III
DIN VDE 0110 Part 2 / 01.89
Overvoltage resistance class
(with inverter connected)
1
DIN VDE 0160 / 04.91
Type of protection
−
Standard
IP20
DIN VDE 0470 Part1 / 11.92 =
^ EN 60529
Interference immunity
IEC 60801-2, IEC 60801-4
Mechanical strength
DIN IEC 60068-2-6 / 06.90
Frequency range
Constant Amplitude of
deflection
acceleration
Hz
mm
m/s
2
(g)
−
stationary
use
10 to 58
more than 58 to 500
0.075
9.8 (1)
−
during
transport
3.5
9.8 (1)
The units can also be operated in load class II. The permissible values must be taken from the following tables.
100%
91%
136%
t/(s)
240s
60s
Load class
ΙΙ
I
(A)
Load class
Ι
Figure 14.1 Power output according to load class II
www
. ElectricalPartManuals
. com