● Bearing plate seals
● Terminal box seals
● Cable glands
● etc.
6.2.14
Finishing connection work
1. Before closing the terminal box, please check that:
– The electrical connections in the terminal box are tight and in full compliance with the
specifications above
– The motor is connected so that it rotates in the direction specified
– The inside of the terminal box is clean and free of any cable debris
– All gaskets and seals are intact
– Unused cable glands must be replaced with certified closures or closed with other
suitable closure types. Comply with the installation and operation conditions specified
in the certificate for these plug elements and check that they have been complied with.
– The pressure relief device is intact Depending on the type of terminal box being used,
the pressure relief device can be implemented either by sealing the slots or by using a
pressure relief diaphragm.
WARNING
Damaged pressure relief device
Water and foreign bodies can penetrate the enclosure if the pressure relief device is
damaged: The degree of protection of the terminal box is no longer guaranteed, a short-
circuit can occur, which can result in death, serious injury or material damage.
● Do not operate the machine with a damaged pressure relief device.
● Any damage may only be repaired after prior discussion with the person responsible
for the safety of the plant or system and only using original parts. Any damage may
only be repaired after prior discussion with the person responsible for the safety of
the installation and only by using original parts.
2. Close the terminal box.
See section "Tightening torques for screw and bolt connections" for the tightening torque
of the fixing bolts for the cover.
6.2.15
Internal equipotential bonding
The equipotential bonding between the ground terminal in the terminal box enclosure and the
motor frame is established via the terminal box metallic contact faces. The contact faces are
protected against corrosion.
Electrical connection
6.2 Connecting
SIMOTICS XP 1MD4/1MD5
Operating Instructions 05/2015
59
Summary of Contents for SIMOTICS XP 1MD4
Page 2: ...13 07 2015 11 26 V8 00 ...
Page 10: ...Table of contents SIMOTICS XP 1MD4 1MD5 10 Operating Instructions 05 2015 ...
Page 12: ...Introduction SIMOTICS XP 1MD4 1MD5 12 Operating Instructions 05 2015 ...
Page 20: ...Safety notes 2 11 Ventilation SIMOTICS XP 1MD4 1MD5 20 Operating Instructions 05 2015 ...
Page 26: ...Description SIMOTICS XP 1MD4 1MD5 26 Operating Instructions 05 2015 ...
Page 50: ...Assembling 5 3 Installing the machine SIMOTICS XP 1MD4 1MD5 50 Operating Instructions 05 2015 ...
Page 74: ...Operation 8 7 Faults SIMOTICS XP 1MD4 1MD5 74 Operating Instructions 05 2015 ...
Page 90: ...Maintenance 9 2 Repair SIMOTICS XP 1MD4 1MD5 90 Operating Instructions 05 2015 ...
Page 110: ...Disposal 11 4 Disposal of components SIMOTICS XP 1MD4 1MD5 110 Operating Instructions 05 2015 ...
Page 126: ...Index SIMOTICS XP 1MD4 1MD5 126 Operating Instructions 05 2015 ...
Page 127: ...AE EC Declaration of Conformity U161 AD EC Declaration of Conformity U163 AA R No 20000h U165 ...