Commissioning
6.2 Checklists
Naturally cooled 1FW6 built-in torque motors
82
Operating Instructions, 07/2017, 6SN1197-0AF02-0BP2
6.2
Checklists
Checklist for commissioning naturally cooled 1FW6 built-in torque motors
Before starting any work, get to know and understand the safety notes and observe the
following checklists.
Table 6- 1
Checklist (1) – General checks
Check
OK
Are all of the necessary components of the configured drive line-up available, correctly
dimensioned, installed and connected?
Are the manufacturer documentation for the system components (e.g. drive system,
encoder, cooling system, brake) and the Configuration Manual "Naturally cooled
SIMOTICS T-1FW6 built-in torque motors" available?
If the 1FW6 built-in torque motor is to be fed from a SINAMICS S120 drive system:
Is the following, current SINAMICS documentation available?
•
SINAMICS S120 Commissioning Manual
•
Getting Started S120
•
S120 Function Manual
•
S120/150 List Manual
If the 1FW6 built-in torque motor is to be fed from a SINAMICS S120 drive system:
Was the Chapter "Checklists for commissioning SINAMICS S" in the SINAMICS S120
Commissioning Manual carefully observed?
Is the motor type to be commissioned known?
(e.g. 1FW6 _ _ _ – _ _ _ _ _ – _ _ _ _)
If the motor is to be fed from a SINAMICS S120 drive system:
If it involves a "third-party motor", are the following motor data known as a minimum?
(A "third-party motor" is a motor that is not saved as standard in the Siemens
commissioning software.)
•
Rated motor current
•
Rated motor speed
•
Motor pole pair number
•
Motor torque constant
•
Maximum motor speed
•
Maximum motor current
•
Motor limit current
•
Motor moment of inertia
•
Motor stator resistance, cold
•
Motor stator leakage inductance
Are the environmental conditions in the permissible range?