● The maximum permissible clamping thickness of 10 mm for the cable lug or strap is not
exceeded
● The minimum required screw-in depth and the tightening torque for the clamping bolt are
listed in the table below. The screw-in depth and tightening torque differ depending on
whether cable lugs or ground terminals are used:
Screw
Screw-in depth
Tightening torque
M12 x 25
> 16 mm
38 Nm
M16 x 35
> 20 mm
92 Nm
Tightening torque of bolts with cable lugs
Screw
Screw-in depth
Tightening torque
M6
> 9 mm
8 Nm
M8
> 12 mm
20 Nm
M10
> 15 mm
40 Nm
Tightening torque of bolts with ground terminals
6.1.6
Radio-frequency grounding for converter operation
In converter operation, the converter emits RF alternating currents. To establish and RF-
specific optimal connection between motor terminal box and motor enclosure, you can use
flexible braided copper flat cables with low impedance and a broad frequency range.
Establish the radio-frequency ground connection with flat cables. Alternatively you can
establish the radio-frequency ground connection with cable lugs.
①
Hexagon bolt
⑤
Hexagon nut
②
Spring washer
⑥
Radio-frequency grounding cable
③
Terminal Board
⑦
Cable lug
④
Grounding conductor
Figure 6-2
High-frequency grounding
You find further information in the "Operation with converter (Page 35)" section.
Electrical connection
6.1 Preparation
SIMOTICS HV M 1RN76308PR900CG0-Z
62
Operating Instructions 07/2018
Summary of Contents for SIMOTICS HV M
Page 2: ...03 07 2018 13 28 V3 00 ...
Page 22: ...Description SIMOTICS HV M 1RN76308PR900CG0 Z 22 Operating Instructions 07 2018 ...
Page 86: ...Operation 8 11 Faults SIMOTICS HV M 1RN76308PR900CG0 Z 86 Operating Instructions 07 2018 ...
Page 122: ...Service and Support SIMOTICS HV M 1RN76308PR900CG0 Z 122 Operating Instructions 07 2018 ...
Page 128: ...Quality documents SIMOTICS HV M 1RN76308PR900CG0 Z 128 Operating Instructions 07 2018 ...
Page 130: ...Additional documents SIMOTICS HV M 1RN76308PR900CG0 Z 130 Operating Instructions 07 2018 ...
Page 135: ......