Technical data and characteristics
6.2 Motor overview/Motor Module assignment/power cables
1FT2 synchronous motors for SINAMICS S120
74
Configuration Manual, 03/2021, A5E50645584B AA
Recommended Motor Module
For every motor, Chapter "Motor overview/Motor Module assignment/power cables
(Page 74)" recommends a Motor Module corresponding to its stall (starting) current.
The maximum torque that can be temporarily achieved using this Motor Module is listed in
the tables of this manual as
M
max inv
.
•
When configuring intermittent or overload operation, check whether a larger Motor
Module is required to provide the necessary peak current.
Tolerance data
The characteristic data listed in the data sheets are subject to a certain amount of scatter. The
following tolerances apply to the characteristic data:
Motor list data
Typ. value
Max. value
Current values
I
0
, I
N
,
I
max
± 3 %
± 7.5 %
Torque values
M
0
, M
N
,
M
max
± 3 %
± 7.5 %
Moment of inertia
J
Mot
± 2 %
± 10 %
The torque-speed characteristics specified in the following chapter relate to the nominal
values at operating temperature.
6.2
Motor overview/Motor Module assignment/power cables
On the following pages, you can find the suitable SINAMICS Motor Modules and MOTION-
CONNECT power cables for the 1FT2.
SINAMICS Motor Module S120 Booksize, DC link voltage 510 V DC to 720 V DC, line voltage 3 AC
380 V to 480 V
Example of an article number for a SINAMICS Motor Module
The following table describes the options that can be selected for the SINAMICS Motor
Module.
Description
Position in the article number
1 2 3 4 5 6 7 - 8 9 10 11 12 - 13 14 15 16
SINAMICS Motor Modules S120
Booksize (example)
6 S L 3 1 2 0
-
Single Motor Module
1
Double Motor Module
2
T E 2 1 - 0 A D
Version release
☐