832-6063.0 * DESCRIPTION SIMOSEC * REVISION 02
17
Description
Momentary-contact
rotary control switch
(option)
The three-position switch is CLOSED-OPENED locally with its motor operating
mechanism. This function is only active when the local-remote switch (option) is in the
‘‘LOCAL“ position.
The momentary-contact rotary control switch is spring-return type and returns to the
center position (M position) automatically.
Bay controller (option)
For information on the bay controller (e.g., SIPROTEC 4), please refer to the instruction
manual for the protective device.
8.5
HV HRC (current limiting) fuse assembly
The HV HRC (current limiting) fuse assembly protects downstream cable runs and/or
devices.
The fuses used in SIMOSEC switchgear are manufactured by Bussman. The fuses
comply with IEC 60282-1 and ANSI/IEEE C37.41. They are a general purpose current
limiting fuse. The time-current characteristics of the fuses comply with the parameters
for E-rated fuses as defined by ANSI C37.46.
The three-position switch-disconnector in the transformer feeder in combination with
Bussmann HV HRC (current limiting) fuses was tested according to ANSI/IEEE C37.20.4.
OPEN
CENTER POSITION (M)
CLOSE
Fig. 13:
HV HRC (current limiting) fuse in transformer panel
a
Dimension e
s
Striker pin
d
HV HRC (current limiting) fuse
f
Extension tube