Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
281
3.5.2.4
Display and statistical data
Read access to the display and statistical data is possible from the register memory area
with function codes 03 and 04.
Individual statistical data can be written via the register memory area with function codes 06
and 16, and be reset, for example.
Max. data length per access: 34 registers.
Table 3- 75 Display and statistical data
Input/holding register Designation
Type
Range
Unit
Access
1)
Info
Address high/low
0x0C00
Coordination
Byte[4]
r
0x0C02
high
Permissible starts - actual
value
Byte
0 .. 255
r/w
low
DM-F - Time until test
requirement
Byte
0 .. 255
1 week
r
0x0C03
Reserved
Byte[2]
r
0x0C04
Number of parameterizations Word
0 .. 65535
r
0x0C05
Number of overload trips
Word
0 .. 65535
r/w
0x0C06
Number of internal overload
trips
Word
0 .. 65535
r
0x0C07
Motor stop time
Word
0 .. 65535
1 h
r/w
0x0C08
Timer 1 actual value
Word
0 .. 65535
100 ms
r
0x0C09
Timer 2 actual value
Word
0 .. 65535
100 ms
r
0x0C0A
Timer 3 actual value
Word
0 .. 65535
100 ms
r
0x0C0B
Timer 4 actual value
Word
0 .. 65535
100 ms
r
0x0C0C
Counter 1 actual value
Word
0 .. 65535
r
0x0C0D
Counter 2 actual value
Word
0 .. 65535
r
0x0C0E
Counter 3 actual value
Word
0 .. 65535
r
0x0C0F
Counter 4 actual value
Word
0 .. 65535
r
0x0C10
Calculator 1 output
Word
0 .. 65535
r
0x0C11
Calculator 2 output
Word
0 .. 65535
r
0x0C12
Reserved
Word[2]
r
0x0C14
Motor operating hours
D word
0 .. 0xFFFFFFFF 1 s
r/w
0x0C16
Internal motor operating
hours
D word
0 .. 0xFFFFFFFF 1 s
r
0x0C18
Device operating hours
D word
0 .. 0xFFFFFFFF 1 s
r
0x0C1A
Number of starts
D word
0 .. 0xFFFFFFFF
r/w
0x0C1C
Number of internal starts CW D word
0 .. 0xFFFFFFFF
r
0x0C1E
Number of internal starts
CCW
D word
0 .. 0xFFFFFFFF
r
0x0C20
Energy W
D word
0 .. 0xFFFFFFFF 1 kWh
r/w
0x0C22
Energy W_F
Float
1 kWh
r
from E03
1) r/w: Value is read/write; r: Value is read-only