18
Environmental conditions
The device is designed for indoor
use only
Ambient Temperature
According to IEC 60688
Operating Temperature Range 32° F to 131° F (0° C to 55° C)
Storage Temperature Range
-13° F to 158° F (-25° C to 70° C)
Max. relative humidity
80 % for temperatures up to 87 °F
decrease linearly to 50 % at 104 °F
Max. altitude above sea level 6,560 ft (2000 m)
Pollution degree
2, no condensation
Additional Technical Data
Internal fuse, primary
Not replaceable
Type T500mA/250V according
IEC 60127 and UL 248-14
Internal fuse, secondary
Not replaceable
Type F2A/125 V according
UL 248-14
Protection class according IEC 60529
Device
-
Front
-
Rear
IP41
IP54 see ordering data
IP20
Personal protection
IP1x
Summary of Contents for SIMEAS P 7KG7550
Page 23: ...21 ...
Page 24: ...22 IP54 Front NOTE All dimensions in mm Width of the device 144 mm ...
Page 51: ...49 Notes ...