13
1.10
Technical Data
Input signals
Only for connection to AC systems
Max. system voltage
600 V (phase-to-phase)
Overload 20%
Frequency of fundamental
component
40 ... 65 Hz
Frequency range f
i
+/- 5 Hz, min. > 30% V
IN
Waveform
Sinusoidal or distorted up to the
21st harmonic
AC current inputs
I
I
3 current inputs
Input current I
i
1 A; 5 A
Continuous overload
Surge withstand capability
10 A
100 A for 1s
AC voltage inputs
V
I
3 voltage inputs
Input voltage V
IN
100/110 V; 190 V; 480 V; 600 V (L-L)
Continuous voltage capability
Surge withstand capability
1.5 x V
IN
2.0 x V
IN
Input resistance (L - N)
2.663 M
Ω
Binary inputs
(optional, only 7KG7660)
Max. input voltage
300 V DC
Current consumption for high
level
1.8 mA
Threshold voltage low
≤
10 V
Threshold voltage high
≥
19 V
Signal delay
max. 3 ms
Analog inputs
(optional, only 7KG7660)
Measuring range
0 to 20 mA DC
Input range
0 to 24 mA DC
Input resistance
50
Ω
±
0.1%
Accuracy
0.5% of the measuring range limit