Program
6.5 Technical specifications of the blocks
Counter module FM 450-1
50
Manual, 02/2014, A5E03648739-02
6.3
The FC DIAG_INF function
Functionality
The FC DIAG_INF reads data record DS1 from the FM 450-1 and makes it available to you
in the DB of the FC CNT_CTRL. Transfer proceeds as follows:
●
If initiation parameter (IN_DIAG=TRUE) the DS1 is read out from the FM°450-1.
●
The DS1 is entered into the DB of the FB CNT_CTRL from DW 54 with the aid of the
SFC RD_REC.
●
The return code of the SFC (RET_VAL) is copied onto the RET_VAL parameter of the
FC DIAG_INF.
●
As soon as the function has been performed, the initiation parameter IN_DIAG is reset
and hence the transfer is reported as completed.
A full description of the SFC RD_REC is to be found in manual°/2/.
Call
The FC DIAG_INF can be called in the cycle and in the interrupt program. However, it is not
expedient to call it in the time-controlled program.
Calling the FC DIAG_INF in the STL and LAD representations is rendered below.
Figure 6-2
Calling the FC DIAG_INF
Parameters of the FC°DIAG_INF
Name
Declaration type
Data type
Meaning
The user...
The block...
DB_NO
INPUT
INT
Number of the data block of
the FC CNT_CTRL
enters this
queries this
RET_VAL
OUTPUT
INT
Return code of the SFC 59
queries this
enters this
IN_DIAG
IN-OUT
BOOL
Initiation bit reads
diagnostics record DS 1
sets and scans
this
resets this
Summary of Contents for simatic s7-400 FM 450-1
Page 8: ...Table of contents Counter module FM 450 1 8 Manual 02 2014 A5E03648739 02 ...
Page 120: ...Spare parts Counter module FM 450 1 120 Manual 02 2014 A5E03648739 02 ...
Page 122: ...References Counter module FM 450 1 122 Manual 02 2014 A5E03648739 02 ...
Page 126: ...Glossary Counter module FM 450 1 126 Manual 02 2014 A5E03648739 02 ...
Page 130: ...Index Counter module FM 450 1 130 Manual 02 2014 A5E03648739 02 ...