Assignment of the DB
10.1 Assignment of the DB
Counter module FM 450-1
Manual, 02/2014, A5E03648739-02
105
Address
Variable
Data type
Initial value Comment
43.7
STS_SW_G
1
BOOL
FALSE
Status SW gate (read user)
44.0
STS_SET
1
BOOL
FALSE
Status digital input SET (read user)
44.1
STS_LATCH
1
BOOL
FALSE
Reserved
44.2
STS_STA
1
BOOL
FALSE
Status digital input START (read user)
44.3
STS_STP
1
BOOL
FALSE
Status digital input STOP(read user)
44.4
STS_CMP1
1
BOOL
FALSE
Status output comparison value 1 (read user)
44.5
STS_CMP2
1
BOOL
FALSE
Status output comparison value 2 (read user)
44.6
STS_COMP1
1
BOOL
FALSE
Reserved
44.7
STS_COMP2
1
BOOL
FALSE
Reserved
45.0
E_BIT3_0
BOOL
FALSE
Reserved
45.1
E_BIT3_1
BOOL
FALSE
Reserved
45.2
E_BIT3_2
BOOL
FALSE
Reserved
45.3
E_BIT3_3
BOOL
FALSE
Reserved
45.4
E_BIT3_4
BOOL
FALSE
Reserved
45.5
E_BIT3_5
BOOL
FALSE
Reserved
45.6
E_BIT3_6
BOOL
FALSE
Reserved
45.7
E_BIT3_7
BOOL
FALSE
Reserved
46.0
ACT_CMP1
1
DINT
L#0
Current comparison value 1 (read user)
50.0
ACT_CMP2
1
DINT
L#0
Current comparison value 2 (read user)
The following diagnostics data are entered by the FC_DIAG_INF
54.0
MDL_DEFECT
BOOL
FALSE
Module faults
54.1
INT_FAULT
BOOL
FALSE
Internal error
54.2
EXT_FAULT
BOOL
FALSE
External error
54.3
PNT_INFO
BOOL
FALSE
Channel error
54.4
EXT_VOLTAGE
BOOL
FALSE
Auxiliary voltage fault
54.5
FLD_CNNCTR
BOOL
FALSE
Front connectors
54.6
NO_CONFIG
BOOL
FALSE
Missing parameters
54.7
CONFIG_ERR
BOOL
FALSE
Faulty parameters
55.0
MDL_TYPE
BYTE
B#16#0
Module type
56.0
SUB_MDL_ERR BOOL
FALSE
Incorrect/missing interface module
56.1
COMM_FAULT
BOOL
FALSE
Communication error
56.2
MDL_STOP
BOOL
FALSE
RUN/STOP operating status indicator
56.3
WTCH_DOG_FAU
LT
BOOL
FALSE
Watchdog (FM)
56.4
INT_PS_FLT
BOOL
FALSE
Internal power supply fault
56.5
PRIM_BATT_FLT BOOL
FALSE
Battery monitoring
56.6
BCKUP_BATT_FL
T
BOOL
FALSE
Backup fault
56.7
RESERVED_2
BOOL
FALSE
Reserved
57.0
RACK_FLT
BOOL
FALSE
Module rack fault
57.1
PROC_FLT
BOOL
FALSE
CPU fault
57.2
EPROM_FLT
BOOL
FALSE
EPROM fault
Summary of Contents for simatic s7-400 FM 450-1
Page 8: ...Table of contents Counter module FM 450 1 8 Manual 02 2014 A5E03648739 02 ...
Page 120: ...Spare parts Counter module FM 450 1 120 Manual 02 2014 A5E03648739 02 ...
Page 122: ...References Counter module FM 450 1 122 Manual 02 2014 A5E03648739 02 ...
Page 126: ...Glossary Counter module FM 450 1 126 Manual 02 2014 A5E03648739 02 ...
Page 130: ...Index Counter module FM 450 1 130 Manual 02 2014 A5E03648739 02 ...