Wiring
4.4 Module status after power is switched on
Counter module FM 450-1
Manual, 02/2014, A5E03648739-02
39
4.4
Module status after power is switched on
Characteristics
After the power supply has been switched on and before any data have been transmitted,
the module status is as follows:
●
Counter inputs with default setting for 5 V differential signals, track B not inverted; single
evaluation (refer to the section "Signal evaluation (Page 100)")
●
0 to +32 bit counting range
●
Counter status zero
●
Counter setting with digital input 1I2 or 2I2 (and zero mark) disabled
●
Input delay for the digital inputs: typically 1
μs
(max. frequency: 200 kHz, minimum pulse width: 2.5
μs)
●
Input delay for 24-V count inputs: typically 1
μs
(max. frequency: 200 kHz, minimum pulse width: 2.5
μs)
●
Outputs 1Q0 and 1Q1 or 2Q0 and 2Q1 switched off
●
Pulse duration = 0
●
No Hardware interrupts set
●
"Continuous counting" mode set
●
Gate function switched off (i.e. gate open)
●
Status messages are updated
This setting corresponds to the default setting of the module.
RESET status
This module status (default setting) is also called RESET status.