Learning units
3.9 9. Step: Configuration of the SINAMICS drive with S7T Config
Sequence
Activity
Result
24
Select parameter "p210" and enter "345".
The smart line module and the motor module of the SINAMICS S120 training case have been especially
equipped for operation on a 230 V system. For this reason, "Parameter p210" of the connected drives must
be set to the following value, which differs from the factory settings:
p210 = 345 V device connection voltage SERVO/VECTOR
The setting of "parameter p210 = 345 V" cannot be calculated by the SINAMICS operating system and is
pre-assigned for the error-free operation of the SINAMICS S120 training case on the 230 V system.
CPU 317T-2 DP: Controlling a SINAMICS S120
Getting Started, 12/2005, A5E00480391-01
3-39