Configuring / Programming
9.4 Configuring a BACnet server
PN/BACnet LINK
Operating Instructions, 10/2017, A5E39895543-AA
63
Note
If the foreign device registration fails with the configured BBMD after the specified number of
retries, the PN/BACnet LINK cannot exchange data via BACnet. Possible causes of a
registry failure may be, for example: Connection interruption, BBMD out of service, BBMD
rejects the registration.
The PN/BACnet LINK does not have automatic restart. If this happens, you must therefore
first switch off PN/BACnet LINK and then switch it on again.
If you expect network problems when using the foreign device registration, set the
connection parameters so that the duration available for registration bridges these network
problems.
9.4
Configuring a BACnet server
When configuring the BACnet server, you define the device object for PN/BACnet LINK as
well as the BACnet I/O objects to be created in PN/BACnet LINK.
Figure 9-3
BACnet server