Example: How to stop the automation program on the CPU
1. Click "STOP" in the operator panel of the CPU.
2. Verify that the virtual signal lamp indicates "STOP" mode.
Additional information
● Manual
SIMATIC; Windows Automation Center RTX; WinAC RTX
7.3.9
How to compile and download the AS data and OS data
Introduction
You compile and download the AS data and OS data in the "Compile and Download Objects"
dialog box of SIMATIC Manager. You can make all settings conveniently and centrally in this
dialog box.
Requirements
● Automation License Manager is installed on the engineering station and the SIMATIC PCS
7 BOX PC.
● SIMATIC Manager is open and your PCS 7 project is displayed in the Component view.
● The menu command PLC > Download to Current Project > Selected Stations has been
executed in NetPro for a selected SIMATIC station.
Note
During the first download operation, the CPU has to be in STOP mode.
The CPU behaves like a standard CPU in PCS 7.
The CPU of the SIMATIC PCS 7 BOX RTX cannot be configured in RUN.
Procedure
1. Select the project in the component view.
2. Select the menu command PLC > Compile and Download Objects..
The "Compile and Download Objects" dialog box opens.
3. Click the plus icon to open all objects in the dialog box.
4. In the tree view of the SIMATIC PC station of SIMATIC PCS 7 BOX RTX, select the
"Configuration" object and select the check boxes in the "Compile" and "Download"
columns.
5. In the tree view of the SIMATIC PC station of SIMATIC PCS 7 BOX RTX , select the "Charts"
object and select the check boxes in the "Compile" and "Download" columns.
Commissioning and configuration of SIMATIC PCS 7 BOX RTX
7.3 Configuring SIMATIC PCS 7 BOX RTX for a single-station system
BOX (V8.1)
Function Manual, 03/2015, A5E32711362-AC
55
Summary of Contents for SIMATIC PCS 7 BOX
Page 6: ...Table of contents BOX V8 1 6 Function Manual 03 2015 A5E32711362 AC ...
Page 8: ...Security information BOX V8 1 8 Function Manual 03 2015 A5E32711362 AC ...
Page 14: ...Preface BOX V8 1 14 Function Manual 03 2015 A5E32711362 AC ...
Page 24: ...WinAC RTX BOX V8 1 24 Function Manual 03 2015 A5E32711362 AC ...
Page 26: ...Web Option for OS with SIMATIC PCS 7 BOX BOX V8 1 26 Function Manual 03 2015 A5E32711362 AC ...
Page 126: ...Establishing the factory state BOX V8 1 126 Function Manual 03 2015 A5E32711362 AC ...