Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
Earth ground ports
100 A/m, continuous
1000 A/m for 1 s
Note
IEC 61000-4-8
Magnetic Field
Enclosure Ports
1000 A/m for 1 s
5
IEC 61000-4-11
Voltage Dips
and Interrupts
AC Power Ports
30% for 1 period
60% for 50 periods
Signal ports
DC Power Ports
IEC 61000-4-12 Damped Oscillatory
AC Power Ports
2.5 kV common, 1 kV
differential mode @1 MHz
3
Signal ports
IEC 61000-4-16
Mains Frequency
Voltage
DC Power Ports
30 V Continuous
300 V for 1 s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
10%
3
IEC 61000-4-29
Voltage Dips
and Interrupts
DC Power Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal ports
2 kV (Failsafe Relay output)
DC Power Ports
1.5 kV
Dielectric Strength
AC Power Ports
2 kV
Signal ports
5 kV (Failsafe Relay output)
DC Power Ports
IEC 60255-5
HV Impulse
AC Power Ports
5 kV
Siemens-specified severity levels.
EMC Immunity Type Tests for IEEE 1613
Note
The RUGGEDCOM RX1511 meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Description
Test Levels
Signal ports
5 kV (Failsafe Relay Output)
DC Power Ports
HV Impulse
AC Power Ports
5 kV
Signal ports
2 kV
DC Power Ports
1.5 kV
Dielectric Strength
AC Power Ports
2 kV
Signal ports
± 4 kV @ 2.5 kHz
DC Power Ports
Fast Transient
AC Power Ports
± 4 kV
RUGGEDCOM RX1511
Installation Manual, 01/2021, C79000-G8976-1056-19