Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
DC Line-to-Line
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
IEC 61000-4-29
30% for 1 period,
60% for 50 periods
IEC 61000-4-11
Voltage Dips
and Interrupts
AC Line-to-Line
100% for 5 periods,
100% for 50 periods
Signal Ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
DC Line-to-Line
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
IEC 61000-4-12
Damped
Oscillatory
AC Line-to-Line
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
Signal Ports
30 V Continuous, 300 V for 1 s
4
IEC 61000-4-16
Mains
Frequency
Voltage
DC Line-to-Line 30 V Continuous, 300 V for 1 s
4
IEC 61000-4-17 Ripple on DC
Power Supply
DC Line-to-Line
15%
3
Signal Ports
2 kV (Fail-Safe Relay output)
DC Line-to-Line
1.5 kV
Dielectric
Strength
AC Line-to-Line
2 kV
Signal Ports
5 kV (Fail-Safe Relay output)
DC Line-to-Line
5 kV
IEC 60255-27
HV Impulse
AC Line-to-Line
5 kV
Siemens-specified severity levels
IEEE 1613 EMC Immunity Type Tests
Note
The RUGGEDCOM RS950G meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports.
Description
Test Levels
Enclosure Contact
± 2 kV, ± 4 kV, ± 8 kV
ESD
Enclosure Air
± 4 kV, ± 8 kV, ± 15 kV
Radiated RFI
Enclosure Ports
35 V/m
Signal Ports
± 4 kV @ 2.5 kHz
DC Line-to-Line
± 4 kV
AC Line-to-Line
± 4 kV
Fast Transient
Earth Ground Ports
± 4 kV
Signal Ports
2.5 kV common mode @ 1 MHz
DC Line-to-Line
2.5kV common, 1 kV differential mode @ 1 MHz
Oscillatory
AC Line-to-Line
2.5 kV common, 1 kV differential mode @ 1 MHz
Signal Ports
5 kV (Failsafe Relay)
HV Impulse
DC Line-to-Line
5 kV
RUGGEDCOM RS950G
Installation Manual, 01/2021, C79000-G8976-1037-06
29