Certification
6.1.9 Other Approvals
6.1.9
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
•
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General
Requirements
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RS950G has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
Description
Test Levels
Severity
Levels
Enclosure
Contact
± 8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
RUGGEDCOM-
specified
severity levels.
Signal Ports
± 4 kV @ 2.5 kHz
Note
DC Line-to-Line
± 4 kV
4
AC Line-to-Line
± 4 kV
4
IEC 61000-4-4
Burst (Fast
Transient)
Earth
Ground Ports
± 4 kV
4
Signal Ports
± 4 kV Line-to-Ground,
± 2 kV Line-to-Line
4
DC Line-to-Line
± 2 kV Line-to-Ground,
± 1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Line-to-Line
± 4 kV Line-to-Ground,
± 2 kV Line-to-Line
4
Signal Ports
10 V
3
DC Line-to-Line
10 V
3
AC Line-to-Line
10 V
3
IEC 61000-4-6
Induced
(Conducted)
RFI
Earth
Ground Ports
10 V
3
40 A/m continuous,
1000 A/m for 1 s
RUGGEDCOM-
specified
severity levels.
IEC 61000-4-8 Magnetic Field Enclosure Ports
1000 A/m for 1 s
5
28
RUGGEDCOM RS950G
Installation Manual, 01/2021, C79000-G8976-1037-06