Certification
6.2 EMC and Environmental Type Tests
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RS416F has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
Description
Test Levels
Severity
Levels
Enclosure
Contact
± 8 kV
4
IEC
61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC
61000-4-3
Radiated RFI
Enclosure
ports
20 V/m
Signal ports
± 4 kV @ 2.5 kHz
DC Power
ports
± 4 kV
4
AC Power
ports
± 4 kV
4
IEC
61000-4-4
Burst (Fast Transient)
Earth
ground ports
± 4 kV
4
Signal ports
2 kV
3
DC Power
ports
± 2 kV line-to-earth,
± 1 kV line-to-line
3
IEC
61000-4-5
Surge
AC Power
ports
± 4 kV line-to-earth,
± 2 kV line-to-line
4
Signal ports
10 V
3
DC Power
ports
10 V
3
AC Power
ports
10 V
3
IEC
61000-4-6
Induced (Conducted) RFI
Earth
ground ports
10 V
3
100 A/m
IEC
61000-4-8
Magnetic Field
Enclosure
ports
1000 A/m for 3 s
5
DC Power
ports
30% for 0.1 s,
100% for 0.05 s
IEC
61000-4-29
IEC
61000-4-11
Voltage Dips and Interrupts
AC Power
ports
30% for 1 period,
100% for 5 periods,
100% for 250 periods
Signal ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
IEC
61000-4-12
Damped Oscillatory
DC Power
ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
40
RUGGEDCOM RS416F
Installation Manual, 04/2021, C79000-G8976-1354-04