Installation and connecting up
3.4 Connector
IE/WSN-PA Link
Compact Operating Instructions, 12/2012, A5E02509264-AD
67
6XEVFULEHU
6XEVFULEHU
1RGHQ
XSWR
SRVVLEOH
7HUPLQDWLQJUHVLVWRUVQHFHVVDU\RQO\
DWKLJKWUDQVPLVVLRQVSHHGDQGZLWK
ORQJFDEOHV
Figure 3-6
Typical 2-wire multipoint network
The figure shows a typical 2-wire multipoint network as operated with the IE/WSN-PA Link.
According to the RS-485 specifications, the transmission cable must be terminated at both
ends of the network. The termination is, however, only intended for high transmission speeds
above 115 kbps and over long cable lengths. For the transmission speeds implemented with
the IE/WSN-PA Link, it is normally not necessary.
Serial connection
Note
With the normal systems, this is as follows:
A = Tx+ and
B = Rx-
Remember that this is sometimes reversed.
Connect 4-wire systems according to the following figure:
Tx +
Tx + = (A)
Rx +
Tx -
Rx -
Rx - = (B)
Note
Use shielded twisted pair cable for the serial connection.
Contact the shield on the serial host and leave it free on the IE/WSN-PA Link.
Make sure that the shielding of the IE/WSN-PA Link is insulated to avoid problems with
grounding.
Summary of Contents for SIMATIC NET IE/WSN-PA Link
Page 4: ...Inhaltsverzeichnis IE WSN PA Link 4 Kompaktbetriebsanleitung 12 2012 A5E02509264 AD ...
Page 42: ...Zulassungen IE WSN PA Link 42 Kompaktbetriebsanleitung 12 2012 A5E02509264 AD ...
Page 44: ...Frequenzbereiche IE WSN PA Link 44 Kompaktbetriebsanleitung 12 2012 A5E02509264 AD ...
Page 46: ...Index IE WSN PA Link 46 Kompaktbetriebsanleitung 12 2012 A5E02509264 AD ...
Page 50: ...Table of contents IE WSN PA Link 50 Compact Operating Instructions 12 2012 A5E02509264 AD ...
Page 88: ...Approvals IE WSN PA Link 88 Compact Operating Instructions 12 2012 A5E02509264 AD ...
Page 90: ...Frequency ranges IE WSN PA Link 90 Compact Operating Instructions 12 2012 A5E02509264 AD ...
Page 92: ...Index IE WSN PA Link 92 Compact Operating Instructions 12 2012 A5E02509264 AD ...