Technical specifications
8.4 Technical data
SIMATIC IPC847D
122
Operating Instructions, 01/2014, A5E32997454-AA
8.4
Technical data
8.4.1
General specifications
General specifications
Order number
6AGA114-2... (for details, refer to the ordering
documentation)
Dimensions
430.4 × 177.4 × 444.4 (W × H × D in mm). You can find
detailed information on dimensions in the section
"Dimension drawings".
Weight
min. 16 kg, max. 23 kg
Supply voltage (V
N
)
100 -240 VAC (-15%, +10%), wide range; with short-term
power failure backup in accordance with NAMUR
Input current AC
Continuous current up to 7 A (during startup up to 30 A for
the duration of 5 ms)
Line voltage frequency
50 to 60 Hz (min. 47 Hz to max. 63 Hz, sinusoidal)
Transient voltage interruption
Min. 20 ms at 93 V
(max. 10 events per hour; recovery time at least 1 s)
Power consumption
Redundant AC power supply:
Max. 300 W at 70% efficiency
AC power supply:
Max. 270 W at 80% efficiency
Power loss / heat emission
300 W = 300 J/s = 0.28 BTU/s
270 W = 270 J/s = 0.26 BTU/s
Current delivery (DC)
+5 V/26 A +3.3 V/24 A, max. accumulated power 190 W
+12 V/15 A +12 V/15 A -12 V/0.2 A +5 Vaux/2 A
Maximum accumulated power of all voltages = 210 W
Noise emission
< 55 dB(A) at 25°C according to DIN EN ISO 7779
all drives in operation, CPU with heavy load
< 45 dB(A) at 25°C according to DIN EN ISO 7779
optical drives not active, CPU at low load
< 35 dB(A) at 25°C according to DIN EN ISO 7779
Fan profile silent, idle desktop, drives are not active,
standard AC power supply
Degree of protection
IP41 at the front and IP20 at the rear to IEC 60529
Dust protection
With closed front door
Filter class G2 EN 779, 99% of particles > 0.5 mm are
filtered
Safety
Protection class
Protection class I according to IEC 61140
Safety regulations
•
IEC 60950-1
•
EN 60950-1
•
UL 60950-1
•
CSA C22.2 No 60950-1-07