Routing
10.3 IP forwarding
Communication
296
Function Manual, 11/2019, A5E03735815-AH
●
For the PC, the IP router, the IO device and the HMI device, the IP addresses of a
standard gateway or the corresponding routes are also entered.
Figure 10-8 Sample configuration
This example configuration results in the following IP routing table for the CPU.
Table 10- 1 IP route table of the CPU
Network destination
Interface
Gateway
0.0.0.0/0
10.10.0.10
10.10.0.1
192.168.1.0/24
192.168.1.1
-
192.168.2.0/24
192.168.2.1
-
10.10.0.0/24
10.10.0.10
-
For IP communication between the PG/PC and the HMI device, you need to set up additional
IP routes to the IP subnet of the HMI device both in the PC and in the IP router. In the HMI
device, you configure the IP address of the CPU interface X1 as the standard gateway.
Summary of Contents for SIMATIC ET 200SP
Page 1: ...Communication ...