Technical specifications
Interface module IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)
Manual, 10/2018, A5E03915895-AH
55
Article number
6ES7155-6AU01-0CN0
•
Monitoring of the supply voltage (PWR-
LED)
Yes; green PWR LED
•
Connection to network LINK (green)
Yes; 2x green link LEDs on BusAdapter
Potential separation
between backplane bus and electronics
No
between PROFINET and all other circuits
Yes
between supply and all other circuits
No
Isolation
Isolation tested with
707 V DC (type test)
Standards, approvals, certificates
Network loading class
3
Security level
According to Security Level 1 Test Cases V1.1.1
Ambient conditions
Ambient temperature during operation
•
horizontal installation, min.
-30 °C; No condensation
•
horizontal installation, max.
60 °C
•
vertical installation, min.
-30 °C; No condensation
•
vertical installation, max.
50 °C
Altitude during operation relating to sea level
•
Installation altitude above sea level, max.
2 000 m; On request: Installation altitudes greater
than 2 000 m
Connection method
ET-Connection
•
via BU/BA Send
Yes; + 16 ET 200AL modules
Mechanics/material
Strain relief
Yes; Optional
Dimensions
Width
50 mm
Height
117 mm
Depth
74 mm
Weights
Weight, approx.
120 g; without BusAdapter
Summary of Contents for SIMATIC ET 200SP IM 155-6 PN/2 HF